• Approval [EEx ia] IIC ATEX II (1) G/D • Main power 230 V AC • Input and output: 4-20 mA • DIN rail mounting
APPLICATION
This converter (input s.i., output non s.i.) with galvanic insulation allows powering of measuring loop or conversion of analogue signal from a transmitter (passive or active) installed in an hazardous area.
TECHNICAL FEATURES
Measuring loop: 1 Main power: 230 V AC ±10 % / 48 ... 62 Hz (indicator of powered unit by a green LED on front) Mounting In safe area Input: s.i. - Output not s.i. Loop powered: For transmitter, 2-wire, active or passive Input signal: from hazardous area 0/4-20 mA Output signal: In and to safe area 0/4-20 mA Galvanic insulation: Between Input/ Output/ Supply: 2500 V AC / 50 Hz Installation: In safe area Case: In ABS Operating temperature -20 ... +60 °C Connectors: Plug-in, clamp terminals Mounting: Rail acc. EN 50022
General Catalog 235-01 06/07/2018 16:48
Intrinsic safety converter BXNT
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France