Attention! You are currently viewing old documentation:
This section of our website concerns references that are no longer manufactured or marketed.
Please use with caution.
Floor standing detector , compact unit
Without moving parts
Built-in relay
Cable output, 5 m long PVC cable
PRINCIPLE
Two electrodes are permanently separated and electrically insulated from each other. The detector monitors the open circuit. When an electrical conductive fluid joins the two electrodes, the resistive detector actuates a relay.
APPLICATIONS
To control if electrically conductive fluids are on site or are not. Single point detection of leakage in basin, drain, etc.
TECHNICAL FEATURES
Main power supply: input for 24 V dc (18-30 V dc) Maximum of 20 mA
Sensitivity: detection within 0.8 to 1 MOhm Detection current: around 1 mA ac Relay: Contact 60 V / 0.5 A max. Dimensions in mm: Length 50 x Width 35 x Height 25 Cable: PVC, length of 5 m (5 wires x 0,14 mm²) Operating temperature: -20°C ... +60°C Mass: 100 g (without cable) EC marks: according (2006/95/EEC) and (89/336/CEE)
General Catalog 544-05 26/03/2022 18:55
Floor leakage alarm device WM24
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France