RDN 11 is an intrinsic safety relay with galvanic insulation. It is designed to relay an ON/OFF signal, from a contact or proximity sensor (DP) located in hazardous area, to the safe area.
Response time ≤ 20 ms Switching frequency 10 Hz max. Signaling: Red LED on front panel (when relay is actuated) Galvanic insulation: Input/ Output/ Mains supply: 2500 V AC; 50 Hz
AGREEMENTS
Intrinsic safety:
EN/CEI 60079-0; EN/CEI 60079-11
[Ex ia] I or [Ex ia] IIC or [Ex ia] IIB
[Ex iaD] I or [Ex iaD] IIC or [Ex iaD] IIB
Safety Ex nA: EN 60079-0 ; EN 60079-15 Certificate ATEX: LCIE 02 ATEX 6104X - INERIS 14 ATEX 3015X Certificate IECEx: IECEx LCI 09.0013X
CE Conformity: The device meets the legal requirements of the current European Directives.
General Catalog 251-01 06/07/2018 16:38
Intrinsic safety relay RDN 11
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France