Attention! You are currently viewing old documentation:
This section of our website concerns references that are no longer manufactured or marketed.
Please use with caution.
4 Limit value Relays for 1 or/and 2 input signal
The forth relay may be used as a Timer
Adjustable hysteresis
2 inputs 4-20 mA, scalable from 0 to 25 mA
Power supply to the sensors
DESCRIPTION
This measuring amplifier is able to control 4 adjustable thresholds for two 0/4-20 mA sensors (2 or 3/4 wires)
TECHNICAL FEATURES
Main power: 230 V ac, code number 232 115 24 V dc on request
Power consumption: Approximately 3 VA Ambient temperature: -10…+45°C Limit relays S1, S2, S3: Adjustable contacts, NO/NC
TIMER / Limit relay S4: by DIP switch configuration use as an adjustable contact, NO/NC or as a pulse TIMER (from 1 s to 24 h)
Switching power: 250 V ac; 2.0 A / 30 V dc; 1.0 A Sensors supply: 24 V dc, max 50 mA; 2 wire technique Housing: Rail DIN mounting 35 x 7.5 mm (DIN EN 50 022), IP40 Dimensions: 22.5 x 100 x 122 mm Electrical connectors: Terminals screw connectors, max. 1.5 mm2 Measuring circuit: 2 channels 0/4-20 mA Accuracy: 0.5 % ± 0.5 Digit Filter: Adjustable from 0.1 s to 3 s Hysteresis: Adjustable from 0 to 99%
Indicator: 2-digit LED display for signal in % 4 LED relay status 1 LED channel 1 or 2 indication
CE Mark: In accordance with low-voltage directive (2006/95/CE), EMC directives (89/336/EEC)
General Catalog 232-03 26/03/2022 18:44
2 channels measuring amplifier for 0/4-20 mA sensors EVEREST 214
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France